LG-5F/LG-10F Mitsubishi Ground Fault Cluster Monitor unit
From “alarm monitoring” to “visible, continuous monitoring”. CC-Link data transmission enables the host monitor system to monitor continuously. This provides the tendency of leakage currents for analyzing abnormalities and facilitating preventive maintenance of facilities.
Feature
- The large-sized LCD displays ground fault levels in 10 circuits simultaneously while displaying leakage current digitally for each circuit.
- The CC-Link transmission enables to check alarm generation in each circuit and remotely monitor measurement values in each circuit.
- The ranges of setting are 30mA to 4A for sensitivity current and 0.1 to 5 seconds for operation time.
- Integrated with the integral circuit against high harmonics and surges, it does not operate erroneously or unexpectedly even if a ground fault current flows in the secondary circuit of the inverter.
- Complies with the high-speed type and time-delay characteristics of the leakage current relays specified in JIS C 8374.
- The integrated self-diagnosis functions generate an output of system alarm in system abnormalities such as when the built-in CPU runs away.

Station type | Remote device station |
---|---|
Number of stations occupied | 1 station |
Protocol version | Ver.1.10/Ver.2.00 |
External dimensions | □144×98mm |
Mass | 0.9kg |
Standard Price | 258,000円(10回路) |