Home > What is CC-Link? > What is CC-Link/LT? > CC-Link/LT specification

CC-Link/LT specification

  4point
modes
8point
modes
16point
modes
Max. number of link points 256points
(512points)*
512points
(1024points)*
1024points
(2048 points)*
Number of link points per station 4points
(8points)*
8points
(16points)*
16points
(32points)*
Link scan time (ms) When 32 stations
are connected
Number
of points
128points 256points 512points
2.5Mbps 0.7 0.8 1.0
625Kbps 2.2 2.7 3.8
156Kbps 8.0 10.0 14.1
When 64 stations
are connected
Number
of points
256points 512points 1024points
2.5Mbps 1.2 1.5 2.0
625Kbps 4.3 5.4 7.4
156Kbps 15.6 20.0 27.8
Communication speed (bps) 2.5Mbps / 625Kbps / 156Kbps
Communication system BITR method
(Broadcastpolling + Interval Timed Response)
Transmission path format T-branch format
Error control system CRC
Max. number of units connected 64 units
Slave station number 1 to 64
Max. number of connected modules
to branch line
8 units / Branch
Inter station length Unlimited
Inter T-branch length Unlimited
Master station connection position Connected to the end of the main line.
RAS function Network diagnosis, internal loopback diagnosis,
slave station disconnection,
and automatic return
Connection cable Dedicated fl at cable (0.75mm2×4),
Dedicated high fl exible cable (0.75mm2×4),
VCTF cable
(JIS C 3306 conformance, 0.75mm2×4)

*This is the address numbers of link points in case of using the same address numbers for input and output.

CC-Link/LT wiring specification

CC-Link/LT wiring specification

Item Specification Remarks
Communication speed
2.5Mbps
625kbps
156kbps
 
Inter station length Unlimited  
Max. number of
connected modules to
branch line
8 units / Branch  
Max trunk line length 35m 100m 500m Cable length between terminators.
(Length of branch cable not included.)
Inter T-branch length Unlimited  
Max. branch line length 4m 16m 60m Overall cable length for one branch line
Overall branch line length 15m 50m 200m Overall length of all the branch lines
·Branch lines can be used together with dedicated fl at cables, VCTF cables or cables exclusively for movable portions.
·Diff erent types of cables cannot be used together within the main line.
·Diff erent types of cables cannot be used together within the same branch line.
·Install the master station at either end of the main line.
·Install a terminating resistor within 20 cm from the master station.
*1:Include the length of any branch from any branch line in the overall branch line length.