CC-Link IE Controller Network specification
| Item | 2 Occupied Stations | |
| Max. number of link points per network | LB | 32768 points |
| LW | 131072 words | |
| LX | 8192 points | |
| LY | 8192 points | |
| Max. number of link points per statio | LB | 16384 points |
| LW | 16384 words | |
| LX | 8192 points | |
| LY | 8192 points | |
| Communication speed | 1 Gbps | |
| Number of connected stations per network | Max. 120 stations | |
| Optical fi ber specifi cations | Optical fi ber cable compatible with 1000BASE-SX (MMF) | |
| Standard | IEC60793-2-10Types A1a.1 (50/125 μm multimode) |
|
| Transmission loss (max) |
3.5 (dB/km) or less (λ=850 nm) | |
| Transmission band (min) |
500 (MHz·km) or higher (λ=850 nm) | |
| Total extension distance (total extension distance of optical cables) |
66 km (with 120 stations connected) | |
| Distance between stations (max) | 550 m (core/clad =50/125 (μm)) | |
| Connector specifi cations | Dual LC type connector | |
| Standard | IEC61754-20: TypeLC connector | |
| Connection loss | 0.3 (db) or less | |
| Polished face | PC polishing | |
| Max. number of networks | 239 | |
| Max. number of groups | 32 | |
| Transmission path form | Double loop | |
CC-Link IE Controller Networks achieve the communication speed of 1 Gbps. Here, the token method is adopted as the data
transfer control method. The token method does not cause any collision of frames in the transmission path, improving the
throughput of communication. Therefore, it is optimal for networks where regular schedule communication is required.