Home > What is CC-Link famiry? > What is CC-Link? > Specification table of CC-Link Ver. 1.10/Ver. 2.00

Specification table of CC-Link Ver. 1.10/Ver. 2.00

If the entire system consists of Ver. 1.10/Ver. 2.00 devices and Ver. 1.10 cables, that provides benefits as follows.

  1. The shortest inter-station cable length is 20 cm under all conditions.
  2. Flexibility of cable length reduces work on wiring and setting devices.
  3. With no extra cable length required when devices are put adjacently,
    you can use space effectively.
  4. Different brand cables can be used within a single system.
    If a system uses modules compatible with Ver. 1.00, 1.10 and Ver. 2.00,
    and cables compatible with Ver. 1.00 and 1.10,
    then follow the Ver. 1.00 specification for maximum overall cable
    extension length and inter-station cable length.
Item Specification
Ver.1.10 Ver.2.00

Control specifi cation

The maximum
number of
link points
Remote I/O
(RX, RY)
2048
points
points each
8192 points each
Remote
register
(RWw)
256
points
2048 words
(Slave station to Master station)
Remote
register
(RWr)
256
points
2048 words
(Master station to Slave station)
Extended cyclic setting - 1time
setting
2times
setting
4times
setting
8times
setting
The number
of link
points per
unit
1
stations
occupied
RX, RY 32 points each
32
points
each
64
points
each
128
points
each
RWw,RWr 4 words
8
words
16
words
32
words
2
stations
occupied
RX, RY 64 points each 96
points
each
192
points
each
384
points
each

RWw,RWr
8 words 16
words
32
words
64
words
3
stations
occupied
RX, RY 96 points each 160
points
each
320
points
each
640
points
each
RWw,RWr 12 words 24
words
48
words
96
words
4
stations
occupied
RX, RY 128 points each 224
points
each

448
points
each

896
points
each

RWw,RWr 16 words 32
words
64
words
128
words
The maximum number of
occupied stations
4 stations
Communication specifi cation Communication speed 10M/5M/2.5M/625k/156kbps
Communication system Broadcast polling system
Synchronization system Frame synchronization system
Encoding system NRZI
Transmission path format Bus format (EIA RS485 conformance)
Transmission format HDLC conformance
Error control system CRC (X16+X12+X5+1)
Number of
units connected
Ver.1.10 64 stations. But it should satisfy the
conditions below
1. Number of all stations
   a+b×2+c×3+d×4≦64
a: Number of units that occupies 1 station
b: Number of units that occupies 2 stations
c: Number of units that occupies 3 stations
d: Number of units that occupies 4 stations
2. Number of units connected
   16×A+54×B+88×C≦2304
A:Number of remote I/O station units
                        ・・・Max. 64 units
B:Number of remote device station units
                         ・・・Max. 42 units
C:Number of local station,
  stand by master station
  and intelligent device
  station units      ・・・Max. 26 units
Ver.2.00 Max. 64 stations.
But it should satisfy the conditions of below.

1. Number of all stations
   (a+a2+a4+a8)+ (b+b2+b4+b8)x2 +     
   (c+c2+c4+c8)x3 + (d+d2+d4+d8)x4≦64

2. Total number of remote I/O points
   (ax32+a2x32+a4x64+a8x128) +
   (bx64+b2x96+b4x192+b8x384) +
   (cx96+c2x160+c4x320+c8x640) +
  (dx128+d2x224+d4x448+d8x896) ≦819

3. Total number of remote register points
   (ax4+a2x8+a4x16+a8x32) +   
   (bx8+b2x16+b4x32+b8x64) +
   (cx12+c2x24+c4x48+c8x96)
 +(dx16+d2x32+d4x64+d8x128)≦2048

a: The number of units with 1 station occupied and 1 time setting
b: The number of units with 2 stations occupied and 1 time setting
c: The number of units with 3 stations occupied and 1 time setting
d: The number of units with 4 stations occupied and 1 time setting
a2: The number of units with 1 station occupied and twice setting
b2: The number of units with 2 stations occupiedand twice setting
c2: The number of units with 3 stations occupied and twice setting
d2: The number of units with 4 stations occupied and twice setting
a4: The number of units with 1 station occupied and 4 times setting
b4: The number of units with 2 stations occupied and 4 times setting
c4: The number of units with 3 stations occupied and 4 times setting
d4: The number of units with 4 stations occupied and 4 times setting
a8: The number of units with 1 station occupied and 8 times setting
b8: The number of units with 2 stations occupiedand 8 times setting
c8: The number of units with 3 stations occupied and 8 times setting
d8: The number of units with 4 stations occupied and 8 times setting

4. Number of units connected
16xA + 54xB + 88xC ≦2304
A: The number of remote I/O station units
 --- Max. 64 units
B: The number of remote device station units
 --- Max. 42 units
C: The number of local station and intelligent
 device station units
 ---Max. 26 units
Remote station number 1~64
Max. overall cable extension length and inter-station cable length

CC-Link Ver 1.10 compatible cable (Using 110Ω terminators)
Communication
speed
Inter-station
cable length
Max. overal cable
extension length
156kbps 20 cm or more 1200m
625kbps 900m
2.5Mbps 400m
5Mbps 160m
10Mbps 100m
If a system uses modules compatible with Ver. 1.00, 1.10 and Ver. 2.00,
and cables compatible with Ver. 1.00 and 1.10, then follow the Ver. 1.00
specifi cation for maximum overall cable extension length and inter-station
cable length.
Connection cable CC-Link Ver. 1.10 compatible cable
(Shielded, 3-core twisted pair cable)
* Mixture of different brand cables is possible only
when they are all Ver. 1.10 compatible cables.

CC-Link Ver. 1.00 model (diff erences from Ver. 1.10)

There are two diff erences in specifi cations between CC-Link Ver. 1.10 and Ver. 1.00 as shown below.
•Max. overall cable extension length and inter-station cable length
•Connection cable
Item Specifi cation
Max. overall cable
extension length
and inter-station
cable length

*1: Inter-station cable length between remote I/O or remote device stations
*2: Inter-station cable length between the master station and a local station or between an intelligent device station and the precedingor following station

CC-Link Ver 1.10 compatible cable (Using 110Ω terminators)
Communication
speed
Inter-station
cable length
Max. overal cable
extension length
   
156Kbps 30cm or over 1m or over(A)
/
2m or over(A)
1200m
625Kbps 600m
2.5Mbps 200m
5Mbps 30cm to 59cm* 110m
60cm or over 150m
10Mbps 30cm to 59cm* 50m
80m
1m or over 100m
(A):1m or longer: In the case of a system comprising only remote I/O or remote device stations (B):2m or longer: In the case of a system comprising local and intelligent device stations
*:If even a cable between remote I/O or remote device stations is to be wired within this range, the maximum overall cable length shown above applies.
Connection cable CC-Link Ver. 1.10 compatible cable
(Shielded, 3-core twisted pair cable)
*Cables of diff erent manufacturers cannot be used together.
CC-Link The left "CC-Link" logo is indicated on CC-Link ver. 1.10 compatible products.
Please contact each manufacturing company for the each CC-Link Ver. 1.10 products.

Page top