Specification table of CC-Link Ver. 1.10/Ver. 2.00
If the entire system consists of Ver. 1.10/Ver. 2.00 devices and Ver. 1.10 cables, that provides benefits as follows.
- The shortest inter-station cable length is 20 cm under all conditions.
- Flexibility of cable length reduces work on wiring and setting devices.
- With no extra cable length required when devices are put adjacently,
you can use space effectively. - Different brand cables can be used within a single system.
If a system uses modules compatible with Ver. 1.00, 1.10 and Ver. 2.00,
and cables compatible with Ver. 1.00 and 1.10,
then follow the Ver. 1.00 specification for maximum overall cable
extension length and inter-station cable length.
| Item | Specification | ||||||||||||||||||||
| Ver.1.10 | Ver.2.00 | ||||||||||||||||||||
|
The maximum number of link points |
Remote I/O (RX, RY) |
2048 points points each |
8192 points each | |||||||||||||||||
| Remote register (RWw) |
256 points |
2048 words (Slave station to Master station) |
|||||||||||||||||||
| Remote register (RWr) |
256 points |
2048 words (Master station to Slave station) |
|||||||||||||||||||
| Extended cyclic setting | - | 1time setting |
2times setting |
4times setting |
8times setting |
||||||||||||||||
| The
number of link points per unit |
1 stations occupied |
RX, RY | 32 points each |
32 points each |
64 points each |
128 points each |
|||||||||||||||
| RWw,RWr | 4 words |
8 words |
16 words |
32 words |
|||||||||||||||||
| 2 stations occupied |
RX, RY | 64 points each | 96 points each |
192 points each |
384 points each |
||||||||||||||||
RWw,RWr |
8 words | 16 words |
32 words |
64 words |
|||||||||||||||||
| 3 stations occupied |
RX, RY | 96 points each | 160 points each |
320 points each |
640 points each |
||||||||||||||||
| RWw,RWr | 12 words | 24 words |
48 words |
96 words |
|||||||||||||||||
| 4 stations occupied |
RX, RY | 128 points each | 224 points each |
448 |
896 |
||||||||||||||||
| RWw,RWr | 16 words | 32 words |
64 words |
128 words |
|||||||||||||||||
| The
maximum number of occupied stations |
4 stations | ||||||||||||||||||||
| Communication speed | 10M/5M/2.5M/625k/156kbps | ||||||||||||||||||||
| Communication system | Broadcast polling system | ||||||||||||||||||||
| Synchronization system | Frame synchronization system | ||||||||||||||||||||
| Encoding system | NRZI | ||||||||||||||||||||
| Transmission path format | Bus format (EIA RS485 conformance) | ||||||||||||||||||||
| Transmission format | HDLC conformance | ||||||||||||||||||||
| Error control system | CRC (X16+X12+X5+1) | ||||||||||||||||||||
| Number
of units connected |
Ver.1.10 | 64
stations. But it should satisfy the conditions below
|
|||||||||||||||||||
| Ver.2.00 | Max. 64 stations. But it should satisfy the conditions of below. 1. Number of all stations (a+a2+a4+a8)+ (b+b2+b4+b8)x2 + (c+c2+c4+c8)x3 + (d+d2+d4+d8)x4≦64 2. Total number of remote I/O points (ax32+a2x32+a4x64+a8x128) + (bx64+b2x96+b4x192+b8x384) + (cx96+c2x160+c4x320+c8x640) + (dx128+d2x224+d4x448+d8x896) ≦819 3. Total number of remote register points (ax4+a2x8+a4x16+a8x32) + (bx8+b2x16+b4x32+b8x64) + (cx12+c2x24+c4x48+c8x96) +(dx16+d2x32+d4x64+d8x128)≦2048 a: The number of units with 1 station occupied and 1 time setting b: The number of units with 2 stations occupied and 1 time setting c: The number of units with 3 stations occupied and 1 time setting d: The number of units with 4 stations occupied and 1 time setting a2: The number of units with 1 station occupied and twice setting b2: The number of units with 2 stations occupiedand twice setting c2: The number of units with 3 stations occupied and twice setting d2: The number of units with 4 stations occupied and twice setting a4: The number of units with 1 station occupied and 4 times setting b4: The number of units with 2 stations occupied and 4 times setting c4: The number of units with 3 stations occupied and 4 times setting d4: The number of units with 4 stations occupied and 4 times setting a8: The number of units with 1 station occupied and 8 times setting b8: The number of units with 2 stations occupiedand 8 times setting c8: The number of units with 3 stations occupied and 8 times setting d8: The number of units with 4 stations occupied and 8 times setting 4. Number of units connected 16xA + 54xB + 88xC ≦2304 A: The number of remote I/O station units --- Max. 64 units B: The number of remote device station units --- Max. 42 units C: The number of local station and intelligent device station units ---Max. 26 units |
||||||||||||||||||||
| Remote station number | 1~64 | ||||||||||||||||||||
| Max. overall cable extension length and inter-station cable length | |||||||||||||||||||||
![]()
If a system uses modules compatible with Ver. 1.00, 1.10 and Ver. 2.00, and cables compatible with Ver. 1.00 and 1.10, then follow the Ver. 1.00 specifi cation for maximum overall cable extension length and inter-station cable length. |
|||||||||||||||||||||
| Connection cable | CC-Link Ver. 1.10 compatible cable (Shielded, 3-core twisted pair cable) * Mixture of different brand cables is possible only when they are all Ver. 1.10 compatible cables. |
||||||||||||||||||||
CC-Link Ver. 1.00 model (diff erences from Ver. 1.10)
There are two diff erences in specifi cations between CC-Link Ver. 1.10 and Ver. 1.00 as shown below.
•Max. overall cable extension length and inter-station cable length
•Connection cable
•Max. overall cable extension length and inter-station cable length
•Connection cable
| Item | Specifi cation | |||||||||||||||||||||||||
| Max. overall cable extension length and inter-station cable length |
![]() *1: Inter-station cable length between remote I/O or remote device stations *2: Inter-station cable length between the master station and a local station or between an intelligent device station and the precedingor following station
*:If even a cable between remote I/O or remote device stations is to be wired within this range, the maximum overall cable length shown above applies. |
|||||||||||||||||||||||||
| Connection cable | CC-Link Ver. 1.10 compatible cable (Shielded, 3-core twisted pair cable) *Cables of diff erent manufacturers cannot be used together. |
|||||||||||||||||||||||||
Please contact each manufacturing company for the each CC-Link Ver. 1.10 products.